Main Features Screw Chiller's human machine interface configures a full touch screen, which enables automatic control and accurate monitoring. The advantages of unit: waterproofdustproof, corrosion resistant, long life. Step or stepless capacity control, the unit ensure that it bring into the most energy-saving effective in any load conditions. Screw Chiller due to use heat copper tube and high efficiency compressor with high effective thermal expansion current-saving device, the unit will operate in stability, longer and effectively. Screw Chiller adopts a reliable safety protection device: to prevent compressor starting frequently, over-current protection, overheat of motor protection, prevent freezing, sight glass in liquid, oil heating protection, phase protection, HV/LV protection, discharge high-temperature protection, safety value, soluble clock, water shut-off protection, and so on. Work Principle Z50 Series Solenoid Valve,Solenoid Control Valve,Hydraulic Solenoid Control Valve,Solenoid Control Valves Huaian Hy-waloil Machinery Co.,Ltd , https://www.hywaloil.com
Explosion -proof screw Chiller adopt the best (semi-hermetic) screw compressor with explosion-proof feature , and operate credibility, high efficiency, easy to maintain, exact volume control, a wide range of application. The system adopts the latest asymmetric rotor profile. Build-in pressure drop lubricant to system with low vibrations, sound emissionshigh sealing performance.
Technical Parameters
Parameters
Model
KDE-75LW
KDE-85LW
KDE-100LW
KDE-120LW
KDE-140LW
KDE-160LW
Nominal Cooling Capacity
Kw/50Hz
298.3
338.3
401.2
482.3
562.3
640.2
Kw/60Hz
343
389
461.4
554.6
646.6
736.2
USRT/50Hz
84.8
96.2
114.1
137.2
159.9
182.1
USRT/60Hz
97.6
110.6
131.2
157.7
183.9
209.4
Kcal/h/50Hz
256538
290938
345032
414778
483578
550572
Kcal/h/60Hz
294980
334540
396804
476956
556076
633132
Input Power
KW
56.8
65
74
90.3
97.6
112.2
Rate Current
A
95.5
106.8
123.5
144.8
169.3
194.4
Max Start-up Current
A
186.3
213.5
263.2
282.3
324.5
356.3
Power
3PH 380V 50Hz(200V/220V/415V/460V50Hz/60Hz)
Refrigerant
Type
R22Â (R134a/R407c)
Control MethodÂ
External-balanced Thermostatic Expansion Valve
Compressor
Type
Semi-Hermetic Screw Type
Start-up Mode
Y-â–³
Capacity Control
0-25%-50%75%-100% stepless adjustment or 0-33%-66%-100%stepless adjustment
Power
KW
56.8
65
74
90.3
97.6
112.2
Condenser
Type
Shell and Tube
Cooling Water Flow
m³/h 50Hz
61.4
69.6
82.3
98.7
115.3
128.7
m³/h 60Hz
69.1
78.3
92.7
111.2
129.8
145.3
 Water Pressure DropÂ
kpa
52
56
57
59
60
60
Inlet/Outlet Pipe Dia.
Inch
3"
4"
4"
4"
5"
5"
Evaporator
Type
Shell and Tube
Chilled Water Flow
m³/h 50Hz
51.4
58.3
69.2
83.2
96.9
110.4
m³/h 60Hz
59.1
67.1
79.5
95.6
111.5
126.9
Water Pressure DropÂ
kpa
52
56
57
59
60
60
Inlet/Outlet Pipe Dia.
Inch
3"
4"
4"
4"
5"
5"
Safety Protection
Compressor over heating protection, over load protection, High/low voltage protection, flow switch protection, reversed and lacking phase protection, anti-freezing protection, fusible plug
Dimension
Length
mm
2450
2750
2750
2750
2750
3460
Width
mm
985
1050
1050
1050
1050
1250
Height
mm
1600
1600
1600
1730
1730
1730
Weight
Net Weight
KG
1300
1560
1720
2030
2200
2410
Running Weight
KG
1480
1780
1960
2250
2430
2470
Note
1. The above red font parameters for special voltage model need to special order; Cooling capacity of R407C unit will be 5% lower than R22 unit
2. Nominal cooling capacity calculated according to: inlet/outlet chilled fluid temperature: 17ºC/12ºC; inlet/outlet cooling water temperature: 30ºC/35ºC
3. Working condition: The temperature range of chilled fluid is from 5ºC to 35ºC; temperature difference between inlet and outlet chilled fluid is from 3ºC to 8ºC.
4. The temperature range of cooling water is from 18ºC to 37ºC; temperature difference between inlet and outlet cooling water is from 3.5ºC to 10ºC.
5. The power distribution and wiring of the installation shall be based on the nameplate or installation instructions of the unit. We reserve the rihgt to modify the above information whithout prior notice
Applications
JECICOOL Â industrial chillers are the perfect solution for any application, in particular for the plastic field, such as : injection molding, extrusion(sheet & profile), blow molding, thermoforming, PET, plastic film, and other industrial field : electroplating (surface treatment), medicine, chemical, hydraulic system, leaser, shoe-making, electronic, print, etc.
Â
Package & Shipping
Use standard export plywood case with forklift truck feet, easy to load and unload
12-15 days to finish the production after receiving the deposit
Shipping by LCL or FCL
After-sales service:
A. 12 months quality warranty since the date of delivery.
B. All extra parts for the machine can be purchased with agent price from COOLDERE.
C. 24 hours working phone call: +8613829879662, Email/ Skype/Trade manager online to support.
D. Professional technical team and sales person give you regarding troubleshooting procedures via Internet and Phone any time when needed.
E. Free and Professional Training at our Factory under the relaxed condition.
Necessary info to Quote
COOLDERE company have one special engineer team for design, they can make the special solution according to your working need, such as customize cooling capacity, special material for ship use, seawater, corrosive, food industry, juice and wine process and etc. Just tell us:Â
A. What's your water composition? or industry
B. What's your temperature range?
C. What's your chilled water flow need?
D. What's the working ambient?
E. What voltage do you need?
1. Differing Refrigerants: R22, R407, R134a can be supplied on request
2. Special voltages: 115V 220V~240V 50 Hz or 60Hz (Single and Three Phase) are available then we can choose the right chiller for you.
Â
Â